• Hz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester

Hz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester

After-sales Service: Yes
Warranty: 1 Years
Type: Tangent Delta Analyzer
Maxcapacity: <1000KN
Accuracy Grade: 0.5
Display: Digital
Customization:
Diamond Member Since 2015

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory

Basic Info.

Model NO.
HZ-2000F
Control
Manual Control
Weight
0-100Kg
Power Source
AC220V
Resolution
Maximum 0.001PF, 4 Valid Figures.
Test Current Range
10μa-1A
Maximum Output Current
200mA
Environment Temperature
-10ºC-50ºC
Relative Humidity
<90%
Overall Dimension
460×360×350mm
External Hv
3PF-1.5μf/10kv 60PF-30μf/0
Tgδ Range
Unlimited, 0.001% Resolution
Set Voltage Range
0.5-10kv
Name
Tangent Delta Analyzer
Transport Package
Wooden Box with Foam Inside
Specification
CE/ISO/IEC
Trademark
HuaZheng
Origin
Hebei, China
HS Code
9030899090
Production Capacity
1000 PCS/Month

Product Description

HZ-2000F Transformer Winding Tan Delta Capacitance And Dissipation Factor Tester

I.Summary of Instrument
Dielectric loss measurement is a very basic method in insulation test, which can effectively find out the whole damp deterioration and local defects of insulation of electrical equipment. It is widely used in electrical manufacturing, electrical equipment installation, handover and preventive test. The measurement of dielectric loss of transformer, mutual inductor, reactor, capacitor, bushing and lightning arrester is the most basic method to measure its insulation performance. The dielectric loss tester has broken through the traditional bridge measurement method, adopting frequency conversion power supply technology, using single chip microcomputer and modern electronic technology to carry out automatic frequency conversion, mode/number conversion and data operation. Strong anti-interference ability, fast test speed, high precision, automatic digitization, easy operation; Power supply adopts high-power switching power supply, output 45Hz and 55Hz pure sinusoidal wave, automatically pressurize, can provide up to 10 kv voltage; Automatic filter 50Hz interference, suitable for substation and other electromagnetic interference large field test. Widely used in the power industry transformer, mutual inductor , casing, capacitor, lightning arrester and other equipment dielectric loss measurement. 
II.Security Measures
1. Read this manual carefully before using this instrument.
2. The operator of the instrument should have general knowledge of the use of electrical equipment or instruments.
3. This instrument can be used both inside and outside, but it should be kept away from places such as rain, corrosive gas, excessive concentration of dust, high temperature and direct sunlight.
4. Instrument should avoid violent vibration.
5. The maintenance, care and adjustment of the instrument should be carried out by professionals.
6. Before any connection, the grounding terminal of the instrument must be reliably connected with the earth with an earth cable.

7. Due to the high voltage generated by the test equipment, the tester must strictly follow the safe operation procedures and prevent others from contacting the high-voltage components and circuits. Direct test personnel must fully understand the high-voltage test circuit, and instrument operation points. Non-engaged testers must stay away from the high-pressure test area, which must be clearly marked with fences or ropes, warning signs, etc.
8. The adjustment, repair and maintenance of the instrument must be carried out without electricity. If it must be live, the operator must be very familiar with the high voltage dangerous parts of the instrument.
9. When the fuse is damaged, the same insurance must be replaced. It is forbidden to replace different types of insurance or directly short circuit the insurance.
10. When the instrument fails, turn off the power switch and wait for one minute before checking.
III.Performance Feature
1. The instrument adopts Fourier transform digital filtering technology to measure capacitance, dielectric loss and other parameters. The precision of the test results is high, which is convenient for automatic measurement.
2. The instrument adopts frequency conversion technology to eliminate 50Hz power frequency interference in the field, and reliable data can be measured even in the environment of strong electromagnetic interference.
3. Use full-touch super large LCD, easy to operate. Full touch LCD screen, large full graphical operation interface, each process is clear, operators do not need additional professional training to use. The whole process can be measured with a touch.
4. Data storage: it is equipped with calendar chip and large-capacity memory, which can save the test results at any time, check the history record at any time, and print out. The current time and storage time can be displayed and printed at any time.
5. Scientific and advanced data management: instrument data can be exported through U disk. Data can be viewed and managed by special software on any PC.
6. The instrument is easy to operate, and the measurement process is controlled by the microprocessor. As long as the appropriate measurement method is selected, the data measurement can be completed automatically under the control of the microprocessor.
7. Integrated model, with standard capacitor and high-voltage power supply, facilitates field testing and reduces field wiring.
8. The measurement accuracy of the instrument is high, which can meet the requirements of oil dielectric loss measurement. Therefore, the measurement of oil dielectric loss can be achieved only by equipping standard oil cup and special test line.
9. It has reverse wiring low-voltage shielding function. When the 220kV CVT bus is grounded, 10kV reverse wiring dielectric loss measurement can be performed on the C11 without removing the wires.
10. Able to do ac withstand test. It is convenient for PT, CT secondary side ac withstand voltage, 400V low-voltage system to do the withstand voltage test.
11. It can identify the frequency of external high voltage power supply (40Hz~70Hz), and allow the use of frequency power supply or serial resonant power supply to conduct large-capacity and high-voltage dielectric loss test.
12. With CVT test function, CVT self-excitation test can be realized, and 4 protection limits of high voltage/current and low voltage/current can be set to ensure the safety of person and equipment.
13. When testing CVT, not only the capacitance and dielectric loss values of C1 and C2 can be automatically tested, but also the total capacitance and dielectric loss values of CVT equipment can be tested
14. With CVT ratio measurement function.It can measure CVT ratio, polarity and phase error.
15. Equipped with thermal printer for printing and output, with calendar clock, convenient for users to produce test report, with U disk output.
16. With a computer interface. A computer can control 32 instruments, which can be integrated into the comprehensive high-voltage test vehicle to achieve measurement, data processing and report output.
  1. Grounding protection function, when the instrument is not grounded or the grounding is bad, the instrument does not enter the normal program, does not output high voltage. Over-current protection, the instrument will not be damaged in short circuit or breakdown.
  2. Electric shock protection function: when the operator of the instrument accidentally touches the electric shock, the instrument will immediately cut off the high voltage to ensure the safety of the test personnel.
IV.Technical Indicators
Accuracy:  Cx: ±(readings×1%+1pF)
tgδ: ±(readings×1%+0.00040)
Anti-interference index: frequency conversion anti-interference, can still achieve the above accuracy under the interference of 200%.
Capacitance range:
Internal high voltage:3pF~60000pF/10kV 60pF~1.5μF/0.5kV
External high voltage: 3pF~1.5μF/10kV 60pF~30μF/0.5kV
Resolution: up to 0.001 pF, 4-bit significant digits
Tgδ range: no limi,The resolution is 0.001%. The capacitance, inductance and resistance can be identified automatically.
Test current range:10μA~5A
Internal high voltage:
Setting Voltage Range:0.5~10kV
Resolution: 1V  Accuracy: ±(1.5%×reading+10V)
Maximum output current:200mA
Boost and drop voltage mode: the voltage is set at will. Such as 5123 v.
Test frequency: 40-70Hz single frequency can be set at will. For example, 48.7 Hz.
50± 0.1Hz to 50±10Hz automatic dual frequency conversion optional setting.
60± 0.1Hz to 60±10Hz automatic dual frequency conversion optional setting.
Frequency accuracy: ±0.01Hz
External high voltage: maximum test current 5A, power frequency or frequency conversion of 40-70Hz during positive connection
Maximum test current 10kV/5A, power frequency or frequency conversion 40-70Hz
CVT self-excitation method low voltage output: output voltage 3~50V, output current 3~30A
CVT ratio measurement:
Ratio accuracy: ±reading × 1%   Ratio measurement range: 10~99999
Phase accuracy: ±0.1°   Phase measurement range: 0~359.9°
Measurement time: about 40s, related to measurement method
Input power: 180V ~ 270VAC, 50Hz±1%,  municipal or generator power supply
Computer interface: standard RS232 interface, U disk socket (automatic U disk storage data).
Printer: micro thermal printer
environment temperature: -10ºC ~ 50ºC
relative humidity: <90%
Overall dimension: 430×330×350mm   
Weight: 28kg
Company Information
HuaZheng Electric Manufacturing (Baoding) Co.,Ltd is the supplier of the State Grid in China.It means we are the supplier of the Chinese Government.And our products spread throughout the whole China.

What's more, our customers come from different countries like America, England, Bulgaria, Brazil, Chile, Malysia, Vietnam and so on.


Our main products are Insulation Oil Tester, Cable Fault Locator, Power Quality Analyzer, High Voltage Generator, High Voltage Capacitor, Testing Transformer and so on.


Hz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester
Hz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester
Customer Visit

Hz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester

ExhibitionHz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester
Similar Recommendation
Hz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester
Hz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor TesterHz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester
Hz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor TesterHz-2000f Transformer Winding Tan Delta Capacitance and Dissipation Factor Tester

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now