1.Model of Series
Model |
Jaw Size (mm) |
Range of Resistance (Ω) |
Range of Current (A) |
Storage Function |
Alarm Function |
HZRC2000+ |
65×32 |
0.01--1200 |
-- |
99 Units |
√ |
HZRC2000A+ |
65×32 |
0.01--200 |
-- |
99 Units |
√ |
HZRC2000C+ |
65×32 |
0.01--1200 |
0.0--20.0 |
99 Units |
√ |
HZRC2100+ |
φ32 |
0.01--1200 |
-- |
99 Units |
√ |
HZRC2100A+ |
φ32 |
0.01--200 |
-- |
99 Units |
√ |
HZRC2100C+ |
φ32 |
0.01--1200 |
0.0--20.0 |
99 Units |
√ |
Note: "√" means available.
2. Ranges and Accuracy of Measurement
Mode |
Range |
Resolution |
Accuracy |
Resistance |
0.010Ω-0.099Ω |
0.001Ω |
±(1%+0.01Ω) |
0.10Ω-0.99Ω |
0.01Ω |
±(1%+0.01Ω) |
|
1.0Ω-49.9Ω |
0.1Ω |
±(1%+0.1Ω) |
|
50.0Ω-99.5Ω |
0.5Ω |
±(1.5%+0.5Ω) |
|
100Ω-199Ω |
1Ω |
±(2%+1Ω) |
|
200Ω-395Ω |
5Ω |
±(5%+5Ω) |
|
400-590Ω |
10Ω |
±(10%+10Ω) |
|
600Ω-880Ω |
20Ω |
±(20%+20Ω) |
|
900Ω-1200Ω |
30Ω |
±(25%+30Ω) |
|
*Current (True-RMS) |
0.00mA -9.00mA |
0.05mA |
±(2.5%+2mA) |
10.0mA -99.0mA |
0.1mA |
±(2.5%+10mA) |
|
100mA -300mA |
1mA |
±(2.5%+20mA) |
|
0.30A-2.99A |
0.01A |
±(2.5%+0.1A) |
|
3.0A-9.9A |
0.1A |
±(2.5%+0.5A) |
|
10.0A-20.0A |
0.1 A |
±(2.5%+1 A) |
Resistance Measurement Frequency: >1KHz
Measured Current Frequency: 50Hz/60Hz
Setting Range of Resistance Alarm Critical Value: 1Ω-199Ω
*Setting Range of Current Alarm Critical Value:1mA -499mA
Instrument safety: IEC/EN61010-1, IEC/EN6010-2-032
Insulation: double insulation
Pollution degree: class II
Overvoltage category: CAT III 150V to ground, Max 20A
Degrees of protection:
-IP30, Group III equipment as per EN 60529 Ed 92
-IK04, as per EN 50102 Ed 95
Dimensions(L×W×H):
-Long elliptic jaw: 285mm×90mm×66mm; (11×4×3 inches)
-Round jaw: 260mm×90mm×66mm;(10×4×3 inches)
Span of Jaw: Long elliptic jaw 35mm; round jaw 32mm
Weight (including batteries): Long elliptic jaw-1160g, Round jaw-1120g
Battery type: 4 ×1.5V alkaline LR6 AA battery
Low battery indication: is displayed
Internal consumption: <50mA
Auto Power off: after 5 minutes of idleness
Display: 4 LCD, sign, decimal point and backlight
Memory size: 99 Units of Reading
Environment (Temperature & Relative Humidity):
-Working: -10°C~55°C, 10%RH-90%RH
-Storage: -20°C ~60°C, below 70%RH
Range shift: Full range automatic shifting
External magnetic field: <40A/m
External electric field: <1V/m
Data upload interface: RS232 (Optional)
HUAZHENG Electric Manufacturing (Baoding) Co., Ltd is established in year of 2008, located at Baoding city, Hebei province, China. It is a professional company specializing in the development and production of electric power testing equipment. Main Product: transformer oil test series, high voltage test series, cable fault location system, microcomputer relay protection test set, etc. All of our products comply with international quality standard and obtained CE and ISO 9001 certificate. Heibei Huanhai Import & Export Trading Co.,Ltd is a trading company established by Huanhai Electric.
We insist on customer orientation and provide you with high quality products, reasonable prices, timely delivery and efficient service. We are willing to work with global clients for joint development and create value and success for our customers continuously.
From the date of purchase within one year instrument,the warranty time is 12 months.This is the piriod of free repair replacement, lifetime supply of maintenance and technical services. If the instrument has been found anomalies or malfunctions please contact us to arrange the most convenient treatment options.