Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 Years |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical parameter
1)Measurement range: 0 ~ 100% (SF6 percentage)
2)Measurement accuracy: ± 0.1 ºC (within 90% ~ 100% range)
3)Resolution: 0.01%
4)Sampling flow: 0.5 ~ 0.8l/min
5)Response time: 15s (90%)
6)Sampling system: built in pressure stabilizing valve, filter and electronic flowmeter
7)Display mode: color touch screen display, all Chinese interface, with backlight
8)Output interface: USB2.0 specification
9)Power supply: built in rechargeable lithium battery (with charging protection device), which can work continuously for 10 hours
10)Size: 320 (mm) × 270(mm) × 140(mm)
11)Operating temperature: - 40 ºC ~ + 80 ºC
Operation steps
1. Start up and warm up for ten minutes. This process can eliminate the influence of ambient temperature on the test results.
2. Connecting SF6 equipment
a) Connect the threaded end of the measuring pipe with the switch connector and tighten it with a wrench;
b) Then insert one end of the quick connector on the test pipe into the sampling port on the purity instrument - < gas inlet >;
c) Connect the exhaust pipe to the air outlet - < gas outlet >.
3. Check the power
When using DC power, please check the battery power displayed in the upper right corner. If the power is less than about 20%, please turn off and continue to use after charging.
4. Start measurement
First, open the meter to measure the needle valve on the pipe, then adjust the flow valve on the panel of the purity tester, adjust the flow to about 0.5L/M, and start measuring the purity value of the SF6 gas.
5. Store data
After the equipment measurement is completed, the data can be saved in the instrument, and press the "data query" key to call out the operation menu.
6. Measuring other equipment
After one equipment is measured, close the needle valve on the measuring pipeline and the regulating valve on the purity instrument. Remove the adapter from the SF6 Electrical equipment. If it is necessary to continue to measure other equipment, continue to measure the next equipment according to the above steps.
7. End of measurement
After the measurement of all equipment, turn off the power supply of the purity instrument.
HuaZheng Electric Manufacturing (Baoding) Co.,Ltd is the supplier of the State Grid in China.It means we are the supplier of the Chinese Government.And our products spread throughout the whole China. What's more, our customers come from different countries like America, England, Bulgaria, Brazil, Chile, Malysia, Vietnam and so on. Our main products are Insulation Oil Tester, Cable Fault Locator, Power Quality Analyzer, High Voltage Generator, High Voltage Capacitor, Testing Transformer and so on. |