The device is mainly designed and manufactured for 10kV, 35kV, 110kV, 220kV cables, 110kV / 80000 kVA main transformer fully insulated, 110kV, 220kV GIS, switches and circuit breakers. The reactor adopts only separate designs, which can not only meet the requirements of high voltage and small current equipment test conditions, but also meet the requirements of low voltage AC voltage test such as 10kV cable. It has a wide range of application, and is the ideal high voltage test equipment of ground, city and county levels and power installation and repair engineering units.
Its is mainly composed of frequency conversion control power supply, excitation transformer, electric reactor and capacitor voltage divider.
HZXB-1000kVA/500kV Technical index
1. Rated voltage
22kV- - -meets the AC voltage withstand test of 10kV cable; working frequency: 30-300Hz,
Test voltage is 22kV, and the test time is 5min;
52kV- - -meet the AC withstand test of 35kV cable; working frequency: 30-300Hz,
Test voltage is 52kV, and the test time is 60min;
128kV- - -meet the AC withstand test of 110kV cable; working frequency: 30-300Hz,
Test voltage is 128kV, and test time is 60min;
216kV- - -Meet the AC voltage withstand test of 220kV cable; working frequency: 30-300Hz,
Test voltage is 216kV, and test time is 60min;
300kV- - -AC withstand voltage test of 110kV GIS, switch and circuit breaker; working frequency: 30-300Hz, test voltage not exceeding 265kV, the test time is 1min;
500kV- - -the AC voltage withstand test of 220kV GIS, switch and circuit breaker; working frequency: 30-300Hz, the test voltage does not exceed 495kV, and the test time is 1min;
200kV- - -AC withstand test of 110kV / 80000 kVA main transformer; working frequency: 45-65Hz, test voltage not exceeding 160kV, test time 1min;
2. Output voltage waveform distortion rate: <1.0%
3. Allowed continuous working time: 60 minutes of working once under rated conditions;
4. Quality factor of the device: Q 30 (f=45Hz)
5, the device output waveform: sine wave
6, input power supply: three-phase 380V or single-phase 220V
7. Frequency adjustment range: 30Hz~300Hz
8. Accuracy of the system measurement is: 1.5%
9. the device has overvoltage, overcurrent, zero start and other protection functions
Test With A Cable Table
Equipment combination Test Object |
Electric reactor 100kVA/50kV ten sets |
Excitation transformer output selection |
test voltage(kV) |
10kV cable 300mm²/6km |
Use ten reactors in parallel (two of which are grounded) |
4kV |
≤22kV |
35kV cable 300mm²/3km |
Use two reactors in series and five grooups in parallel |
4kV |
≤52kV |
110kV cable 630mm²/1km |
Use three reactors in series and three groups in parallel |
4kV |
≤128kV |
220kV cable630mm²/0.5km |
Use five reactors in series and twoe groups in parallel |
8kV |
≤216kV |
110kV GIS,switch,circuit breaker |
Use six reactors in series |
8kV |
≤265kV |
220kV GIS,switch,circuit breaker |
Use ten reactors in series |
25kV |
≤495kV |
110kV/80000kVA The main transformer is fully insulated |
Use four reactors in series |
8kV |
≤160kV |