Manual test functions |
Can arbitrarily set the AC amount of various voltages, current amplitude, phase, and set various fault types of parameters |
Test the electrical performance of relays and protection with AC voltage (including phase voltage, line voltage, zero sequence voltage, positive sequence voltage, negative sequence voltage), AC current (including phase current, line current,) amplitude, phase, frequency, impedance and other variables. | |
The step size can be manually controlled, and the step size can be changed by any setting variable | |
Changes in output can be controlled | |
Monitor changes in the input volume | |
Action time can be tested | |
Multiple continuous state tests |
Provides a variety of state sequence settings |
Provide a variety of time control, input control, manual trigger for state switching | |
Can set various types of faults, including single grounding, two-grounding, interphase short circuit, three-phase short circuit. Fault type Instantaneous fault, permanent fault, transformational fault, and can control the fault transition time | |
Can provide constant current, constant impedance and other test methods | |
It can simulate the opening and closing time of the short-circuit device | |
Can provide a separate voltage output as zero sequence voltage or line extraction voltage As zero sequence voltage can be set to ±3U0 or ±3√3U0; The amplitude and phase of the voltage can be set at will when the line extraction voltage is tested |
|
Can check the opening, opening and logical relationship of the action behavior of relays, protection and safety automatic devices | |
The amplitude and phase of voltage and current can be set arbitrarily | |
Can set the status parameters of various faults | |
Can control each switching quantity separately | |
Dedicated test function | Low cycle load shedding |
Concurrent test | |
Harmonic test | |
AC sampling test | |
Millisecond timing function | |
Remote test |
Product Model | HZJB-1700 |
AC voltage output | 4 channels:0-130V continuously adjustable66V by default |
Output precision | Accuracy:0~5V Accuracy error≤±2mV,5V~120V Accuracy error≤±0.1%±2mV;Resolution:1mV |
Carrying capacity | ≥30VA/phase |
Response time | Voltage 5V~130:THD%≤0.5%,The voltage rise and fall time is less than 100µ s |
Phase | 0-360° continuously adjustable;Accuracy 0.2°;Resolution 0.1° |
AC current output | 3 channels:0-10A |
Output precision | Accuracy:0.2~0.5A, Error≤2mA,0.5~10A Accuracy error≤0.1%±2mA;Resolution:1mA |
Current output time | T330 current output time calculation formula is as follows:: (Ia*Ia+Ib*Ib+Ic*Ic)*t = 600 seconds Typical current setting output time is as follows: Ia=1A, Ib =0A, Ic=0A output time is 600 seconds Ia=1A,Ib =1A,Ic=1A output time is 200 seconds Ia=5A,Ib=5A,Ic=5A output time is 90 seconds Ia=10A, Ib=10A, Ic=10A output time is 6 seconds |
Carrying capacity | ≥20VA/phase |
Response time | Current 0.5A~Imax:THD% ≤0.5%;The current rise and fall time is less than100µ s |
Phase | 0-360° Continuously adjustable;Accuracy 0.2°;Resolution 0.1° |
Output frequency | 0-650Hz,It can simulate 11 harmonics |
Accuracy | Frequency range:10-65Hz Accuracy<1mHz;65 Hz ~250Hz Accuracy<10mHz |
Opening & Closing volume | Opening volume:2 channels Isolation voltage is 500V, the null contact is compatible with 32V~250V potential, and the polarity is automatically recognized; Closing volume:Type of 2 channels closing volume: optocoupler opening, time resolution is 0.1ms. |
Adapter | DC 16.8V 5A |
Built-in battery & Endurance | Built-in 20 amh lithium battery; Normal use of 8 hours |
Instrument size & Weight | Less than 2.75kg(hand-held)size:255x210x78(mm) |