high current generator (referred to as the current riser), our company developed its own test equipment, it sets the advantages of similar products at home and abroad in one, the use of numerical control technology, strong anti-interference ability, and the previous generation of current riser, due to the use of low power consumption, large capacity of autoregulator and high permeability of the core converter, with large output power, small size, Light weight and other advantages. Mainly used for thermal relay, motor protector, contactor, breaker, air switch, switch cabinet, circuit breaker, protective screen calibration; Used for primary bus protection and various current transformer ratio test projects, is widely used in electric power, railway, petrochemical, metallurgy and mining enterprises scientific research, production and electrical test site.
1. Name and classification
(1) Name: Primary Current Injection Tester.
(2) Environmental group: Group III instruments in GB6587.1-86 "General Outline of Environmental Test for Electronic Measuring Instruments" (can be used in outdoor environment).
(3) Input AC 50Hz, 220V.
(4) Output single-phase 0-1000A AC current; The current can be smoothly and continuously adjustable, the accuracy is higher than 0.1 level;
The output current is the standard sine wave, the burr is small, better than the power system requirements indicator standard, ripple system
The number is less than 0.3%.
(5) Output current mode: the true RMS value is continuously adjustable;
(6) Output waveform: standard sine wave;
(7) Output opening voltage: 5-6V.
(8) Current accuracy: Each current can be smoothly and continuously adjustable, and the accuracy is higher than 0.5. The current voltmeter is displayed as the true effective value, with high precision and high stability;
(9) Current stability: 0.1%;
(10) Current waveform distortion: THD 1%;
(11) Protection Settings: overcurrent, overvoltage;
(12) The current action time of the measured component can be measured, and the locking action time can be recorded synchronously. Automatic identification of normally open and normally closed contacts.
(13) Measuring range: 0.0001S --9999.9999S, accuracy: 0.0001S
(14) Power: 5000VA