Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model: hztrf500-0.0005 (ac500kv, dc500kv)
Rated frequency: 50hz-200hz
Cooling mode: onan
Stage: 2
Single capacitance: 1000pf, single resistance: 500M
Rated capacitance: 500pf rated electrical resistance: 1000M
Rated AC voltage: 500kV rated DC voltage: 500kV
Nominal AC partial voltage ratio: 2000 / 1 nominal DC partial voltage ratio: 10000 / 1
Running time: long time
The Dielectric loss: < 0.2% AC / DC voltage divider picture
Temperature coefficient: < 0.0004
Overvoltage capacity: the overvoltage shall not cause any insulation damage of the test transformer under the condition of 110% uh for 60s;
Measurement accuracy AC: <± 1% measurement accuracy DC: <± 0.5%
Running time: long
Top pressure equalizing cover structure: the pressure equalizing cover is made of high-quality LY2 pure aluminum plate, and the welding process adopts sub arc welding machine to ensure that aluminum oxidation does not occur when placed in the air for a long time. Its radius of curvature contains 550kV power frequency voltage, and corona does not occur on the pressure equalizing cover. In particular, the parts arranged above require hot-dip galvanizing after metal processing to prevent iron oxidation in the air, Over a long period of time, the above components will be oxidized, resulting in corona discharge.
Volume: φ250/φ850×2600mm
Weight: < 250kg
Company Information