I. Introduction
This instrument is a special equipment to eliminate the remanence of large power transformers, and has the functions of demagnetization and verification demagnetization. It plays an extremely important role in protecting the transformer from the impact of magnetizing inrush current, putting it into operation safely and prolonging the life of the transformer.
After the power transformer undergoes operations such as voltage ratio, DC resistance measurement, and no-load test, residual magnetism will remain in its core. If the residual magnetism is not treated, it may have many adverse effects on the relay protection device of the power transformer and the primary equipment. Excessive magnetizing inrush current can cause the transformer to fail to close, and the transformer itself mechanically vibrates, causing displacement of the winding structure, affecting the life of the power transformer and even causing permanent damage to it.
To this end, our company has developed a series of transformer degaussing products. It is an earlier manufacturer of degaussing instruments and has accumulated a lot of practical experience.
The power transformer degaussing analyzer is a new generation of degaussing analyzer independently developed by our company. Using advanced and reasonable composite current method technology, it can not only quickly demagnetize the power transformer transformer, but also quantify the residual magnetism detection. The detection and elimination of residual magnetism are automatically completed at one time. For three-phase transformers, only one phase can be demagnetized, which is more time-saving and efficient.
1,Main technical features
l The instrument adopts advanced compound current degaussing method, the current impact is small during the degaussing process.
l The degaussing efficiency is high, and only one phase of the three-phase transformer can be eliminated, which greatly saves time.
l With manual degaussing and automatic degaussing.
l It has the functions of initial remanence detection and remanence detection after demagnetization, and the measurement of demagnetization and remanence can be completed by one connection.
l The demagnetization process progress percentage and demagnetization progress indicator bar are intuitive and clear, quantify the remanence rate, and display the remanence curve before and after demagnetization.
l The wiring is simple, and the DC resistance test line can be directly used for demagnetization.
l Adopt digital current adjustment, and the current control precision is high.
l It is controlled by a 5-inch color touch screen, which is easier to operate.
l The test results are automatically stored, and the data before and after degaussing are completely recorded, without manual storage.
l The report can be printed directly and stored in a U disk.
l The analysis software has a high degree of humanization and intelligence. After setting the parameters, all measurement tasks can be completed by pressing a button.
l The software interface is simple and intuitive, and the menus for analysis, storage, report export, and printing are clear at a glance.
2,Main Specifications
l lInput type: current method
l lOutput voltage: Vpp-40V, automatically adjusted during testing
l lOutput current: 5A, 4A, 3A, 2A, 1A, can be selected arbitrarily
l lRemanence: 0-100%
l lDegaussing progress: 0-100%
l lDegaussing effect: residual magnetic rate ≤5%
l lMinimum resolution: 0.1%
l lSupply voltage: AC100V-240V ±10%
l lFrequency: 50Hz/60Hz
l lWorking environment: -10~50 ≤85%RH
l lWeight: 6kg
3,Main features of test analysis software
l Using an embedded system, the software has no risk of poisoning.
l lThe test data is saved in a directory, and the management of the test data is simple and convenient.
l lThe test system can directly print data.
l lSupport U disk data export function.
l lThe software has a high degree of intelligence. After the input and output signals are connected, all measurement tasks can be completed by pressing a key.
l lThe software interface is simple, intuitive and practical.
From the date of purchase within one year instrument, is a product quality problem free repair replacement, lifetime supply of maintenance and technical services. The instrument has found anomalies or malfunctions please contact us to arrange the most convenient treatment options.